Ac contactor B9-30 series specification
Ac contactor B9-30 series specification
Ac contactor B9-30 applicable scope
Ac contactor Models B9, B12, B16, B25 and B30 are mainly suitable for ac 50Hz power system with voltage up to 660V and current up to 8.5, 11.5, 15.5, 22 and 30A respectively. The AC contactor can be used to provide long distance on and off lines and is suitable for frequent control of ac motors.

The contactor is applicable to the following working conditions:
1. The altitude should not exceed 2000 meters.
2. The upper limit of ambient air temperature is +40 ° C, and the average value within 24 hours cannot exceed +35 ° C; the lower limit of ambient air temperature is -5 ° C.
3. The air relative humidity of ac contactor of Shanghai electrical appliances shall not exceed 50% when the highest temperature is +40℃. A relatively high relative humidity can be allowed at a lower temperature, but the average minimum temperature of the wettest month should not exceed +25℃, and the average maximum relative humidity of that month should not exceed 90%. Necessary measures should be taken when condensation occurs on the AC contactor due to temperature changes.
4. The vertical tilt should not exceed 5°.
Ac contactor B9-30 technical parameters
The basic parameters of the contactor are shown in the figure below.

Ac contactor is suitable for eight-hour working system, uninterrupted working system, intermittent periodic working system and short working system, etc. Its operating frequency is 600 times/hour when AC3 is under load, and 300 times/hour when AC4 is under load.
The release voltage of the contactor shall not be higher than 75% of the rated control supply voltage, and the lowest release voltage shall not be lower than 20% of the rated control supply voltage.
The contactor's suction coil of model B9, B12 and B16 starts at 60VA and holds at 9VA and 2.2W respectively. The contactor's suction coil of Model B25 and B30 has a power consumption starting of 85VA and a holding capacity of 10VA and 3W, and the energy efficiency grade conforms to GB21508.
Ac contactor B9-30 installation wiring
The contactor's appearance and installation size are shown in the following figure.

◆ The equipment can be installed with two M4 screws and a gasket and spring pad, or with a standard rail, the dimensions of which are shown in the figure above.
◆ The conductor may be a single strand or multiple strands,
Electrical contactor B9, B12 model of the main circuit conductor cross section is 2.5 mm, B16 model of the main circuit conductor cross section is 4 mm, B25, B30 model of the main circuit conductor cross section is 10 mm.
The wiring terminal marks of ac contactor are as follows:
1. Incoming end of main circuit: 1/L1, 3/L2, 5/L3, 7/L4.
2. Main circuit outline end: 2/T1, 4/T2, 6/T3, 8/T4.
3. Auxiliary circuit usually enters the line end 13 and leaves the line end 14.
4, auxiliary circuit normally closed line end 21, exit end 22.
◆ Coil inlet end A1, outlet end A2.
◆ The wiring terminal adopts the combination screw, and the special washer is used as the wiring platen. During wiring, insert the loose wire of the combination screw under the wiring platen, and then tighten the combination screw.
Ac contactor B9-30 is safe to use
◆ Before use, the rated voltage and frequency of the selected coil must be consistent with the voltage and frequency of the control power supply, and the AC contactor of Shanghai People's electrical appliances must be installed correctly. If not properly selected, faults will occur and the equipment will burn down.
◆ When wiring, do not let foreign matter fall into the inner part of the contactor, so as not to cause the movable part to get stuck or cause short circuit and other fault phenomena.
◆ The AC contactor has the function of indicating the state of operation. When the indicating rod (that is, the contact bracket) drops, it will be connected, and when the rod rises, it will be disconnected. The power must be cut off during maintenance.
◆ The fit of contactor short circuit Protection apparatus (SCPD) is stipulated as "type 2" fit, model B9-B20 shall match the FUSE of RT16-35, model B30 shall match the fuse of RT16-50.
Optional accessories for AC contactor B9-30
◆CA7 auxiliary contact: The contactor can stack CA7 monopole or quadrupole auxiliary contact on the top wedge fast. Four monopole CA7 can be installed, which are ca7-01 normally closed and CA7-10 normally open respectively. The quadrupole CA7 can be fitted with one, and there are six fixed combinations for normally open and normally closed.
Rated operating voltage of CA7 auxiliary contacts of AC contactor is up to 660V and rated control capacity is 450VA (AC-15). The rated operating voltage is 220V and the rated control capacity is 30VA (DC-13).
◆CA7 Installation Method:
1. Push the wedge at the top of CA7 groove against the positive AC contactor and push the foot towards the arrow direction;
2. Transfer CA7 check into the top cover slot;
3. Press the white brake piece flat and lock it into the long square hole of the top cover;
4.Push the forefinger to the contact support without any jamming. The specific operation is as shown in the figure below.

◆CA7 disassembly method:
1. Lift the white stop to make it trip;
2. Exit by the direction of arrow;
3.Turn out the top slot, and the specific operation is shown in the figure below.

◆VB30 mechanical interlock: This accessory can perform mechanical interlock on two AC contactors of Shanghai People electrical appliances that have been connected into electrical interlocks to ensure the reliability of reversible operation. Reversible contactor sets can be formed by using two contactors of the same type plus a VB30.

◆ INSTALLATION method of VB30: First fix the VB30 to an AC contactor and then install another one (assembled according to the arrow number). After completion, check that any one of the two devices should be closed, and the other one should not be closed, and the two cannot be closed at the same time. The specific operation and installation size are shown in the figure above.