ABB soft starter PSE fault code and troubleshooting
ABB soft starter PSE fault code and troubleshooting
ABB soft starter PSE starting problems and failures
◆Fault status: LED is off and LCD is blank.
Cause: The power supply voltage Us is not connected.
Remedy: Refer to Chapter 5 Wiring and Chapter 11 Circuit Diagram of ABB Soft Starter PSE Installation and Commissioning Manual for wiring.
◆Fault status: Green LED is steady or flashing and LCD is dim.
Cause: The LCD backlit display automatically turns off.
Remedy: Press any key on the keyboard to recover.
ABB soft starter PSE trip event failure

PSE fault indication code for ABB soft starter
◆ Software fault state: red fault LED stable bright or flashing and LCD fault code SF20.
Cause: Software failure.
Exclusion methods:
1. Disconnect and reconnect the control power supply voltage Us to restart;
2. If the problem still exists, please contact ABB low-voltage Department.
Cause: Soft starter parameter failure.
Exclusion methods: Check the PSE parameter and select the PSE soft starter type that corresponds to it.
◆ Bypass failure status: red fault LED stability bright and LCD failure code SF3x.
Reason: The by-pass contact is PSE18 closed after transportation (applicable only. PSE170).
Exclusion methods: Check the PSE parameter and select the PSE soft starter type that corresponds to it. Control the supply voltage at terminals 1 and 2, wait for four seconds, then switch on the main loop voltage at terminals L1, L2 and L3.
Cause: Bypass contactor/relay not on.
Elimination method: Check and replace the relay. Please contact ABB low voltage department for replacement.
Cause: Short circuit in SCR.
Method of exclusion: Check and replace the SCR. Please contact ABB low voltage department for replacement.
◆ Bypass disconnected state: red fault LED stability bright and LCD fault code SF4x.
Cause: Insufficient capacity of control power supply circuit.
Elimination method: Check the control supply voltage.
Cause: Bypass relay/contactor on or off.
Elimination: Check and replace relay or contactor. Please contact ABB low voltage department for replacement.
◆ Thermal overload status of soft starter: red fault LED stability bright and LCD fault code SF50.
Cause: the THYristor overheats, if the fault still exists after reset, and the thermistor temperature is too high.
Exclusion methods:
1. Check whether the fan works normally;
2. Check whether the cooling and ventilation channels are blocked by debris and dust;
3, check whether the ambient temperature is too high, more than 40 degrees need melting;
4. Check whether the installation Angle exceeds 30 degrees;
5. Check the number of times of STARTING and stopping of ABB soft starter PSE within an hour, whether it meets the requirements.
◆ Phase failure state: red fault LED stability bright and LCD fault code EF1x.
Cause: Fuse blown.
Method of elimination: Check and replace the three-phase fuse.
Cause: Loss of one - or multiphase working current.
Method of elimination: Check and ensure the normal operation of grid voltage.
Cause: Main circuit contactor or circuit breaker is disconnected.
Exclusion methods: Check and close contactor/circuit breaker or any external switching equipment.
Cause: The main contactor was broken prematurely during shutdown.
Exclusion methods:
1. Control the main loop contactor with terminal 4(operation signal);
2. Increase the delay time before the contactor is broken;
3. If the soft stop function of ABB soft starter is not needed, please set the buck time to 0.
◆ Poor state of power grid quality: Red fault LED stable bright and LCD fault code EF20.
Cause: Excessive interference of power supply network at work.
Method of elimination: Check and ensure the normal operation of grid voltage.
Cause: All three-phase working voltage is missing.
Method of elimination: Check and ensure the normal operation of grid voltage.
◆ Current missing fault status: red fault LED stable bright and LCD fault code EF3x.
Cause: operating current is too low, or missing in one or multiple phases.
Method of elimination: Check and ensure the normal operation of grid voltage.
Cause: Phase loss on the power side or motor side.
1. Check and provide the correct working power grid; 2. See phase failure EF14 for details.
Cause: The thyristor does not conduct.
Exclusion methods: Check and replace printed circuit board/SCR, contact local ABB low voltage department for replacement.
Cause: Motor load is too small (current is out of the range measured by ABB soft starter PSE).
Method of elimination: Check whether the soft starter conforms to the motor power.
◆ Bus fault state: red fault LED stability bright and LCD fault code EF40.
Cause: Bus wiring or bus adapter attachment failure.
Exclusion methods:
1. Check whether the bus adapter model used is correct;
2. Check whether the bus adapter is connected correctly;
3. Check whether the bus attachment is connected correctly;
4. Reset all existing events.
Cause: Bus communication not working.
Exclusion methods:
1. Check whether the bus adapter model used is correct;
2. Check whether the bus adapter is connected correctly;
3. Check whether the bus attachment is connected correctly;
4. Reset all existing events.
Cause: PLC not working.
Exclusion methods: 1. Adjust PLC to operation mode; 2. 2. Check the CONFIGURATION of PLC.
Cause: System bus control parameters without a bus are turned on.
Exclude method: Set the bus control parameter to close.
◆ Low power supply voltage state: red fault LED stable bright and LCD fault code EF50.
Cause: The soft starter control supply voltage is too low at terminals 1 and 2.
Elimination method: Check and provide the correct control supply voltage.
Cause: The control power supply network is temporarily missing.
Elimination method: Check and control the power supply network.
◆ High-current fault status: red fault LED stable bright and LCD fault code EF6x.
Cause: Operating current higher than 8*Ie.
Exclusion methods:
1. Check whether the motor is blocked or has difficulty in operation;
2. Check motor bearings and connectors;
3. Check whether the motor load is too heavy;
4, check the insulation on the motor winding;
5. Replace the motor.